FICHTNER India Project NHPTL HIGH POWER SHORT CIRCUIT TEST FACILITY AT BINA (MP) Subject Doc. No. Rev. Section HEAT LOAD CALCULATION ETHS&PS/620P90801/ED2.131.001.B A Sheet No. Description 1 OF 20 References / Remarks Annexure-1: Estimation of Heat load calculation for proposed MV Switchgear Building & Control Room Building for Electrical equipments 1.1 33 KV Switchgear This Swotchgear having four Nos. of 33 KV switchgears (a). Incomer module with 2500A breaker: 2 Nos. Incomers of 25
Categories
Published
of 20
All materials on our website are shared by users. If you have any questions about copyright issues, please report us to resolve them. We are always happy to assist you.
Related Documents
Share
Transcript
   FICHTNER  India1 OF 20 Annexure-1: Estimation of Heat load calculation for proposed MV Switchgear Building & Control Room Building for Electrical equipments1.1 33 KV Switchgear  This Swotchgear having four Nos. of 33 KV switchgears(a). Incomer module with 2500A breaker:2 Nos. Incomers of 2500A VCB, having 2 CT's of 15VA burden, 5 indicating lamps, 4 meters,1 PT-100 VA burden, 4 auxiliary contactors & 4 relays & width of panel is 1200 mmBreaker loss=3x2500 2 x60x10 -6 =wattsCT+PT=(2x15+100)x0.1=wattsIndicating lamps==wattsNegligible, since the typeMeters=4x3=wattsof indication lamp is Aux. contactors=4x4=wattsassumed as LED typeRelays=4x2=wattsBusbars=0.0724x2500x3x1.2=wattsThe heat loss one incomer feeder=wattsTherefore, total heat loss for 2 incomer feeders =watts=KW (b). Outgoing module with 1250A breaker:2 Nos. outgoing feeders of 1250A VCB, having 2 CT's of 15VA burden, 5 indicating lamps,4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relays & width of panel is 1200 mmBreaker loss=3x1250 2 x60x10 -6 =wattsCT+PT=(2x15+100)x0.1=wattsIndicating lamps==wattsNegligible, since the typeMeters=4x3=wattsof indication lamp is Aux. contactors=4x4=wattsassumed as LED typeRelays=4x2=wattsBusbars=0.0724x1250x3x1.2=wattsThe heat loss one outgoing feeder=wattsTherefore, total heat loss for 2 outgoing feeders= watts = KW1.2 Lighting Load = KW  Assumed 1.3 Power Cable = KW  Assumed Therefore Total Heat Load For MV Building = KW 12128FORM T9-P REV-A130 0.5 1212652 1304 8 References / Remarks Sheet No.Project 1822 3643 130Rev.Doc. No.SubjectNHPTL HIGH POWER SHORT CIRCUIT TEST FACILITY AT BINA (MP) ASectionETHS&PS/620P-90801/ED2.131.001.BHEAT LOAD CALCULATION1125652 Description3.641.30.726.17 281326 File Name Originator / Dept. KR / EL .Date11/7/2014   FICHTNER  India2 OF 20 References / Remarks Sheet No.Project Rev.Doc. No.SubjectNHPTL HIGH POWER SHORT CIRCUIT TEST FACILITY AT BINA (MP) ASectionETHS&PS/620P-90801/ED2.131.001.BHEAT LOAD CALCULATION Description2. Control Room Building2.1 CRP Panels =wattsAssumed Therefore, total heat loss for 11 CRP = KW2.2 MLDB & ELDB =wattsAssumed Therefore, total heat loss for 3 ACDBs=KW2.3 Lighting Load = KW  Assumed 2.4 Power Cable = KW  Assumed 2.5 AC Automatic Transfer Switch (ATS) This Switchgear having four Nos. of 415V switchgears Incomer & Outgoing module with 2000A breaker:2 Nos. Incomers & 2 Nos. Outgoing feeders of 2000A ACB, having 2 CT's of 15VA burden,5 indicating lamps, 4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relaysBreaker loss=3x2000 2 x60x10 -6 =wattsCT+PT=(2x15+100)x0.1=wattsIndicating lamps==wattsNegligible, since the typeMeters=4x3=wattsof indication lamp is Aux. contactors=4x4=wattsassumed as LED typeRelays=4x2=wattsBusbars=0.0724x2000x3x1.8=watts Therefore, total heat loss for ATS=KW2.6 AC Normal Supply Panel (a). Incomer module with 2000A breaker:1 No. Incomer of 2000A ACB, having 2 CT's of 15VA burden, 5 indicating lamps, 4 meters,1 PT-100 VA burden, 4 auxiliary contactors & 4 relaysBreaker loss=3x2000 2 x60x10 -6 =wattsCT+PT=(2x15+100)x0.1=wattsIndicating lamps==wattsNegligible, since the typeMeters=4x3=wattsof indication lamp is Aux. contactors=4x4=wattsassumed as LED typeRelays=4x2=wattsThe heat loss one incomer feeder=wattsTherefore, total heat loss for 1 incomer feeder  =KW (b). Outgoing module with 1000A MCCB:1 No. outgoing feeder of 1000A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relaysBreaker loss=wattsCT+PT=(2x15+100)x0.1=wattsIndicating lamps==wattsNegligible, since the typeMeters=4x3=wattsof indication lamp is Aux. contactors=4x4=wattsassumed as LED typeRelays=4x2=wattsThe heat loss one outgoing feeder=wattsTherefore, total heat loss for 1 outgoing feeder= KW 8121287208245 0.25 Project Subject13012012 4.04 FORM T9-P REV-ARev.Section 2.75References / Remarks Project SubjectDoc. No.720 1.35 13450 0.5 -13012NHPTL HIGH POWER SHORT CIRCUIT TEST FACILITY AT BINA (MP)HEAT LOAD CALCULATION 4.5 Doc. No.Rev. Description SectionSheet No.ETHS&PS/620P-90801/ED2.131.001.B250977765 0.77 20012 File Name Originator / Dept. KR / EL .Date11/7/2014   FICHTNER  India3 OF 20 References / Remarks Sheet No.Project Rev.Doc. No.SubjectNHPTL HIGH POWER SHORT CIRCUIT TEST FACILITY AT BINA (MP) ASectionETHS&PS/620P-90801/ED2.131.001.BHEAT LOAD CALCULATION Description (c). Outgoing module with 630A MCCB:3 Nos. outgoing feeders of 630A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relaysBreaker loss=wattsCT+PT=(2x15+100)x0.1=wattsIndicating lamps==wattsNegligible, since the typeMeters=4x3=wattsof indication lamp is Aux. contactors=4x4=wattsassumed as LED typeRelays=4x2=wattsThe heat loss one outgoing feeder=wattsTherefore, total heat loss for 3 outgoing feeders= KW (d). Outgoing module with 400A MCCB:2 Nos. outgoing feeders of 400A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relaysBreaker loss=wattsCT+PT=(2x15+100)x0.1=wattsIndicating lamps==wattsNegligible, since the typeMeters=4x3=wattsof indication lamp is Aux. contactors=4x4=wattsassumed as LED typeRelays=4x2=wattsThe heat loss one outgoing feeder=wattsTherefore, total heat loss for 2 outgoing feeders= KW (e). Outgoing module with 300A MCCB:2 Nos. outgoing feeders of 300A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relaysBreaker loss=wattsCT+PT=(2x15+100)x0.1=wattsIndicating lamps==wattsNegligible, since the typeMeters=4x3=wattsof indication lamp is Aux. contactors=4x4=wattsassumed as LED typeRelays=4x2=wattsThe heat loss one outgoing feeder=wattsTherefore, total heat loss for 2 outgoing feeders= KW (f). Outgoing module with 200A MCCB:1 No. outgoing feeder of 200A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relaysBreaker loss=wattsCT+PT=(2x15+100)x0.1=wattsIndicating lamps==wattsNegligible, since the typeMeters=4x3=wattsof indication lamp is Aux. contactors=4x4=wattsassumed as LED typeRelays=4x2=wattsThe heat loss one outgoing feeder=wattsTherefore, total heat loss for 1 outgoing feeder= KW 1001214501212 0.21 40Doc. No.NHPTL HIGH POWER -12 DescriptionReferences / Remarks 2002458513Rev.SectionProject Subject128FORM T9-P REV-A 0.09 6013810513120128 0.74 130128NHPTL HIGH POWER SHORT CIRCUIT TEST FACILITY AT BINA (MP)HEAT LOAD CALCULATIONETHS&PS/620P-90801/ED2.131.001.B-Sheet No.0 0.29  File Name Originator / Dept. KR / EL .Date11/7/2014   FICHTNER  India4 OF 20 References / Remarks Sheet No.Project Rev.Doc. No.SubjectNHPTL HIGH POWER SHORT CIRCUIT TEST FACILITY AT BINA (MP) ASectionETHS&PS/620P-90801/ED2.131.001.BHEAT LOAD CALCULATION Description (g). Outgoing module with 160A MCCB:1 No. outgoing feeder of 160A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relaysBreaker loss=wattsCT+PT=(2x15+100)x0.1=wattsIndicating lamps==wattsNegligible, since the typeMeters=4x3=wattsof indication lamp is Aux. contactors=4x4=wattsassumed as LED typeRelays=4x2=wattsThe heat loss one outgoing feeder=wattsTherefore, total heat loss for 1 outgoing feeder= KW (h). Outgoing module with 125A MCCB:2 Nos. outgoing feeders of 125A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relaysBreaker loss=wattsCT+PT=(2x15+100)x0.1=wattsIndicating lamps==wattsNegligible, since the typeMeters=4x3=wattsof indication lamp is Aux. contactors=4x4=wattsassumed as LED typeRelays=4x2=wattsThe heat loss one outgoing feeder=wattsTherefore, total heat loss for 2 outgoing feeders= KW (i). Outgoing module with 100A MCCB:2 Nos. outgoing feeders of 100A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relaysBreaker loss=wattsCT+PT=(2x15+100)x0.1=wattsIndicating lamps==wattsNegligible, since the typeMeters=4x3=wattsof indication lamp is Aux. contactors=4x4=wattsassumed as LED typeRelays=4x2=wattsThe heat loss one outgoing feeder=wattsTherefore, total heat loss for 2 outgoing feeders= KW (j). Outgoing module with 80A MCCB:1 No. outgoing feeder of 80A MCCB, having 2 CT's of 15VA burden, 5 indicating lamps,4 meters, 1 PT-100 VA burden, 4 auxiliary contactors & 4 relaysBreaker loss=wattsCT+PT=(2x15+100)x0.1=wattsIndicating lamps==wattsNegligible, since the typeMeters=4x3=wattsof indication lamp is Aux. contactors=4x4=wattsassumed as LED typeRelays=4x2=wattsThe heat loss one outgoing feeder=wattsTherefore, total heat loss for 1 outgoing feeder= KW 20001212 0.15 73FORM T9-P REV-A2865 0.07 1312Doc. No.128130128 0.15 1381212885 0.09 1273 DescriptionReferences / Remarks 4013028 SHORT CIRCUIT TEST FACILITY AT BINA (MP)HEAT LOAD CALCULATION90801/ED2.131.001.B-Sheet No.NHPTL HIGH POWER SHORT CIRCUIT TEST ETHS&PS/620P-Project SubjectRev.Section-HEAT LOAD CALCULATIONSheet No. File Name Originator / Dept. KR / EL .Date11/7/2014
We Need Your Support
Thank you for visiting our website and your interest in our free products and services. We are nonprofit website to share and download documents. To the running of this website, we need your help to support us.

Thanks to everyone for your continued support.

No, Thanks